ENCLOSURE
The construction of Enclosure is prefabricated with mild steel. The metal base will be made of hot dip galvanised steel and ensure rigidity and easy transportation and installation. Ventilation apertures will be sufficient for natural ventilation. Double doors will be equipped with key lock and rubber seals. It is weather and water proof with degree of protection IP33 and suitable for
all climates.

MAJOR COMPARTMENTS/COMPONENTS OF COMPACT SUBSTATION:
- Ring Main Unit
- Distribution Transformer
- LV Distribution Board

RING MAIN UNIT
Medium Voltage Ring Main Unit is type-tested, metal enclosed, SF6 insulated indoor
switchgear installation. It is equipped with two ring switches and one transformer fuse
switch. It verifiably meet all the demand encountered in network operation in virtue of
the following features:
- High degree of personnel safety
- High degree of reliability, availability and freedom from maintenance
- Compact and small size
- Problem-free disposal of the SF6 gasOperation not affected by environmental effects
- Conform to IEC standards
- IEC Publication No. 298, 694, 265, 420 and 129
- Equipped with Earth leakage detector (optional)

 


DISTRIBUTION TRANSFORMERS
The Distribution transformer is used to duly-couple with the LV Distribution Board and Ring Main Unit in the Compact Substation. The medium voltage terminals are coupled by cables/busbars directly to the Ring Main Unit and the low voltage terminals are coupled by cables/busbars directly to the LV Distribution Board. LV DISTRIBUTION BOARD The LV panel is equipped with tinned copper busbars, incoming link units, outgoing fuse units, and instrument panel for meeting and indication.

APPLICATION
Compact Substation is normally used for power distribution in light industry estate, housing, etc.

TECHNICAL DATA

Rated Power (kVA)

500

750

1000

Transformer Ratio (kV)

11/0.433

11/0.433

11/0.433

Transformer

Rated Power (kVA)

500

750

1000

Type

 

Hermetically Sealed Type

LV Distribution Board

Rated Link Unit

1 x 800 Amps

1 x 1600 Amps

1 x 1600 Amps

Rated Fuse Unit

6 x 400 Amps

8 x 400 Amps

8 x 400 Amps

Ring Main Unit

Type

SF6-insulated

SF6-insulated

SF6-insulated

Housing

Cladding

Mild Steel

Mild Steel

Mild Steel

Base

Channel Steel

Channel Steel

Channel Steel

Overall Dimension
(not to exceed)

Length (mm)

1860

1860

1860

Width (mm)

2660

2660

2660

Height (mm)

2050

2050

2050

Installation Location